Permit: T14CM08955

Parcel: 129010870


Addresses:

2337 E 19TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/14/2015 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
01/12/2015 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/12/2015 MECHANICAL - INTERMEDIATE Not ready for Inspection 1. WHITE WIRE NOT TO BE USED AS A HOT LEG
2. SERVICE RECPT REQUIRED ON ROOF
3. PVC NOT PROPERLY TERMINATED. MUST BE 6" A.G.
4. PVC TO BE COATED FOR UV PROTECTION
5. GASLINE IN ATTIC RESTRICTING RETURN AIR
6. SEAL ALL DUCT ON ROOF
7. GAS NOT COMPLETE
8. W/H NOT INSTALLED AT THIS TIME
9. PVC SUPPORT NOT TO EXCEED 48' HORIZ