Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
11/13/2015 FIRE - FINAL Approved
10/27/2015 FIRE - FINAL Cancelled WILL NOW TAKE ALARM COMPANIES TEST OF ALARM SYSTEM PER KB.
10/08/2015 FIRE - FINAL Partial Approval 1. SW EXIT DOOR STICKING
2. REMOVE LOCK ON SW EXIT GATE WITH PANIC HARDWARE
3. NEED COVER PLATE ON OUTLET IN THE KITCHEN
4. ARROW ON THE EAST EXIT SIGN SHALL POINT NORTH
5. ONLY 1 METHOD TO UNLATCH EAST COURTYARD EXIT GATE AND NO SURFACE MOUNTED OR SLIDE BOLTS. NO LATCHES WITH PAD LOCKS.
6. NEED TO TEST ALARM SYSTEM WITH NEW DIALER, SMOKES, PULLS, AND AV'S
7. FIRE ALARM IS NOT LOCKED OUT IN BREAKER BOX
8. BREAKER BOX MUST BE LABELED
9. NEED TO TEST EMERGENCY LIGHTING WHEN BREAKER BOX IS LABELED APPROPRIATLY.
07/31/2015 FIRE - FINAL Denied This is an E occupancy with occupant load above 50
1.)1008.1.10 Panic and fire exit hardware - All exits shall have panic hardware.
2. No other locks or opening devices allowed on doors with panic hardware.
3. All gates on exterior leading to a public way shall have panic hardware ( can not reduce the level of fire protection in exit path to a public way)
4. fire extinguisher tops may not be above 60 inches ( 5 ft high)
5. exit signs not operating on battery back up power
6. no emergency lighting installed to light interior exit path
7. fire alarm panel is not connected to devices ( inside wiring has been disconnected)
8. security door on kitchen requires two methods of unlatching.
9. commercial electric convection in kitchen requires a type 2 hood installed.
10. [B] 1008.1.5 Floor elevation.
There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal (2-percent slope). Interior door removed so it is just a passage in the wall, however it drops immediatlely on the other side 4 inches.
11. Fire Alarm system shall be inspected and tested per stamped plans and shall pass.