Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
Permit Number - T14CM08825
Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2015 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | 200 psi for 2 hours approved | |
08/06/2015 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | Only called for site on piping so they can bury piping before rain, thrust blocking in place, tracer wire in place, depth 30" to 40" deep and all metal wrapped with plastic PVC wrap. Okay to bury all unground pipe Still need to do 200 PSI test for 2 hours and flush using a burlap to make sure no foreign material is in piping. |