Permit: T14CM08627

Parcel: 205942920

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T14CM08627

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/21/2015 FRAMING Approved IVRS - Inspection :*
10/20/2015 FRAMING Denied 1. STRAP AND BLOCK ALL ABS HORIZANTAL PIPING EVERY 4'-0" WITH APPROVED METHOD
2. RANGE AND DRYER RUNS NEED TO BE SECURD WITHIN 6" OF BOX
3. FURNACE B-V4ENT IS TOUCHING ELECTRIC CABLE TO CONVIENCE LIGHT.
4. SHALL PRIVIDE ENGINEER RFI FOR OVER NOTCH TOP PLATE 2ND FLOOR WHERE B-VENT IS LOCATED.
5. SEAL PENETRATION @ NORTH WALL T&P DRAIN
10/19/2015 FRAMING Denied 1. SHALL PROVIDE BLOCKING ANS TRAP FOR ABS PIPING EVERY 4'-OO". P-TAP IS NOT APPROVBED MATERIAL.
2. SEAL ALL PENETRATIONS ON STUCCO MESH
3. WATER HEATER B-VENT NOT SECURED
4. FIRE STOP ALL PENETRATIOS THROUGH TOP PLATE
5. SEAL BOTTOM IST FLOOR PLATE
6. STRAP DOWN GAS LINE
7. INSPECTION STOPPED