Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T14CM08565
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/03/2015 | FIRE - ALARM FINAL | Approved | APPROVAL PER NIKI SPRINGER | |
08/18/2015 | FIRE - ALARM FINAL | Denied | 1. All duct smoke detectors shall be on the fire alarm monitoring system. IFC 907.3 & 907.3.1 2. Need to monitor the ansul system on the fire alarm monitoring system IFC 904.3.5 |