Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/10/2015 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection :* |
| 08/04/2015 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 08/04/2015 |
BUILDING - FINAL |
|
Partial Approval |
PROVIDE A HOSE CLAMP ON DRAIN. PAINT EXPOSED PVC. SEAL HOLES AT LINESET. RELOCATE CONDENSOR TO ALLOW 36" CLEARANCE AT PANEL. PROVIDE A PROTECTIVE COATING ON ANY EXPOSED ARMAFLEX. SECURE ELEC CONDUIT TO CONDENSOR. MAX BREAKER FOR A/C IS 15 AMP |