Permit: T14CM08365

Parcel: 104080870


Addresses:

850 W AUTO MALL DR

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
12/11/2015 FIRE - FINAL Approved
11/23/2015 FIRE - FINAL Partial Approval 1. Okay to move in and use the offices in the warehouse ONLY!
2. Okay to move in furniture into the sales floor no public use, need to test em lights again 2 failed on sales floor and bathroom. Still need egress em lights install.
3. Need to test the roll down fire door for the 2 hour separation wall.
4. Need to install fire extingushers
11/18/2015 FIRE - FINAL Denied 1. Emergency lights needed in new warehouse office area
2. Add exit sign in hallway from retail to warehouse
3. Repair or replace emergency lights on sales floor 6 drop down lights failed
4. Need egress lighting install outside exit doors northwest & northeast corner
5. Need fire extinguishers 1 for every 75 foot travel distance 2A 10BC type mounted min 4" to max 5 feet from top of extinguisher handle above floor. If extinguisher is more than 40 pounds in weight max 3.5 feet.