Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2014 | ELECTRIC - FINAL | Partial Approval | NEED TO SEE FINAL TIE IN | |
| 12/18/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/18/2014 | ELECTRIC - FINAL | Denied | - SUB-PANELS NEED NEUTRALS/GROUNDS ISOLATED - USE APPROVED CABLE CONNECTOR AT BACK PANEL PENETRATION - VERIFY WATER/GAS PIPE BOND - #6 ALUM RATED AT 50 AMPS PER 75' COLUMN 310-15 NEC |