Permit: T14CM08010

Parcel: 13321075A


Addresses:

10 N WILMOT RD


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM08010

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/05/2015 FIRE - FINAL Approved
06/03/2015 FIRE - FINAL Denied There is no fire alarm system for this building and there are strobes in the bathrooms that are tied into two seperate duct detectors? IFC 901.4.5 prohibits equipment with the appearance of fire safety device that does not perform that function.
1.The builder may elect to install an alarm system and apply for the permit and submit plans for review OR
2. The strobe devices shall be removed from the bathrooms, wires capped off and covered with a proper cover plate.