Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2015 | FIRE - FINAL | Approved | ||
| 06/03/2015 | FIRE - FINAL | Denied | There is no fire alarm system for this building and there are strobes in the bathrooms that are tied into two seperate duct detectors? IFC 901.4.5 prohibits equipment with the appearance of fire safety device that does not perform that function. 1.The builder may elect to install an alarm system and apply for the permit and submit plans for review OR 2. The strobe devices shall be removed from the bathrooms, wires capped off and covered with a proper cover plate. |