Permit: T14CM07897

Parcel: 11446015B

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T14CM07897

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/13/2016 FIRE SPKLR - FINAL Approved 1) painted heads have been replaced
2.) inspectors test - flow was 39 seconds
3.)Main drain test - 81 psi static
75 - residual flowing main drain
4) water heater room and riser room separated by wall / heads approved
01/07/2016 FIRE SPKLR - FINAL Cancelled Not ready
01/06/2016 FIRE SPKLR - FINAL Denied 2 sprinklers in the back hallway are covered with orange protective devices.
Upright sprinkler in front of stage area is painted black (see notes on plans)
upright sprinkler behind stage area up stair ladder is painted black(see plans)
Sprinkler in riser room and water heater room are not 6 feet apart or separated by a wall (see plans)
01/04/2016 FIRE SPKLR - FINAL Not ready for Inspection NO RESPONSIBLE PARTY ONSITE