Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T14CM07897
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/13/2016 | FIRE SPKLR - FINAL | Approved | 1) painted heads have been replaced 2.) inspectors test - flow was 39 seconds 3.)Main drain test - 81 psi static 75 - residual flowing main drain 4) water heater room and riser room separated by wall / heads approved |
|
01/07/2016 | FIRE SPKLR - FINAL | Cancelled | Not ready | |
01/06/2016 | FIRE SPKLR - FINAL | Denied | 2 sprinklers in the back hallway are covered with orange protective devices. Upright sprinkler in front of stage area is painted black (see notes on plans) upright sprinkler behind stage area up stair ladder is painted black(see plans) Sprinkler in riser room and water heater room are not 6 feet apart or separated by a wall (see plans) |
|
01/04/2016 | FIRE SPKLR - FINAL | Not ready for Inspection | NO RESPONSIBLE PARTY ONSITE |