Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T14CM07579

Parcel: 117110170

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM07579

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/23/2015 FIRE - FINAL Approved
01/12/2015 FIRE - FINAL Denied 1. FIRE ALARM PERMIT REQUIRED-ADDITIONAL NOTIFICATION DEVICES NEEDED.
2. FIRE SPRINKLER WORK NOT COMPLETED
3. PANIC HARDWARE REQUIRED ON SECOND EXIT
4. FINISH EMERGENCY LIGHTING
5. PROVIDE DOCUMENTATION OF REVISED BUILDING PERMIT WITH PLANS SHOWING FIRE REVIEWED
6. PROVIDE DOCUMENTATION THAT A TYPE II HOOD IS ALLOWED BECAUSE MENU STATES EGGS, SAUSAGE, HAM BEING COOKED. GREASE LADEN VAPORS REQUIRE A TYPE I HOOD WITH A FIRE EXTINGUISHING SYSTEM
7. FIRE PUMP TEST REPORT NEEDED FOR BUILDING, DID NOT SEE IT ON ANNUAL FIRE SPRINKLER REPORT.
ADDED RE-INSPECTION FEE FOR FIRE.