Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM07579
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2015 | FIRE - FINAL | Approved | ||
01/12/2015 | FIRE - FINAL | Denied | 1. FIRE ALARM PERMIT REQUIRED-ADDITIONAL NOTIFICATION DEVICES NEEDED. 2. FIRE SPRINKLER WORK NOT COMPLETED 3. PANIC HARDWARE REQUIRED ON SECOND EXIT 4. FINISH EMERGENCY LIGHTING 5. PROVIDE DOCUMENTATION OF REVISED BUILDING PERMIT WITH PLANS SHOWING FIRE REVIEWED 6. PROVIDE DOCUMENTATION THAT A TYPE II HOOD IS ALLOWED BECAUSE MENU STATES EGGS, SAUSAGE, HAM BEING COOKED. GREASE LADEN VAPORS REQUIRE A TYPE I HOOD WITH A FIRE EXTINGUISHING SYSTEM 7. FIRE PUMP TEST REPORT NEEDED FOR BUILDING, DID NOT SEE IT ON ANNUAL FIRE SPRINKLER REPORT. ADDED RE-INSPECTION FEE FOR FIRE. |