Permit: T14CM07567

Parcel: 140260380

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T14CM07567

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2016 FIRE SPKLR - OH PIPING & HYDRO Approved
12/30/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval SPRINKLER HEAD LOCATION ISSUE RESOLVED. TCO OK FOR STOCKING ONLY - 11-20-15
11/16/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 200 psi test for 2 hours -APPROVED
Correct the following areas as marked in orange on approved plans:
1. Sales floor as marked on plans taped heads, blocked heads by piping, head blocked by hanger.
2. Missing heads x2 sales floor by service deli area.
3. Meat cooler area head blocked by conduit piping.
4. Receiving area heads blocked by conduit need to correct coverage.
5. Still need to pressure test 2 inch piping front of building for outside canopy.