Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM07531
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2015 | FIRE - FINAL | Approved | ||
| 11/23/2015 | FIRE - FINAL | Partial Approval | Partial Approval 1. need address per pima county address code 2. need lock box on sprinkler riser room door 3. post FDC sign over FDC's ( or near to ) 4. Place NFPA diamond on door to medical gas room with highest hazard ( oxidizer) 5. place exterior handle on exit door ( south) that has panic hardware on inside ( egress side)- currently missing outside handle. |
|
| 11/18/2015 | FIRE - FINAL | Continued |