Permit: T14CM07503

Parcel: 114469490

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM07503

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2015 FIRE - FINAL Approved
02/19/2015 FIRE - FINAL Partial Approval Temp C of O approved for use of building to get finals the following shall be completed:
1. Fire alarm monitoring system installed for the sprinkler system
2. Paint the outside water supply line piping for the sprinkler system.
3 . Install the pressure relief valve on the riser.
02/18/2015 FIRE - FINAL Denied Contractor called he asked if they can get a Temp C of O before the fire alarm monitoring is installed, I advised him that TFD will give a temp C of O but to get final they will need to have an approved working fire alarm monitoring system installed.
02/17/2015 FIRE - FINAL Denied 1. Install pressure relief valve on riser
2. Paint outside piping to riser
3. Need UL/FM approved fire alarm monitoring system install
4. This building was a "B" occupy but now changed to a I-4 occupy classification, need to install battery back egress lighting per IFC & IBC 1006.3
5. Need to install battery back lighting outside each egress door landing per IBC & IFC 1006.3 #3 .
6. Need fire extinguisher posted every 75' travel distance and one for every 1500 sq. ft of building size. Needs to be a 2A-10BC type.