Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM07503
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2015 | FIRE - FINAL | Approved | ||
| 02/19/2015 | FIRE - FINAL | Partial Approval | Temp C of O approved for use of building to get finals the following shall be completed: 1. Fire alarm monitoring system installed for the sprinkler system 2. Paint the outside water supply line piping for the sprinkler system. 3 . Install the pressure relief valve on the riser. |
|
| 02/18/2015 | FIRE - FINAL | Denied | Contractor called he asked if they can get a Temp C of O before the fire alarm monitoring is installed, I advised him that TFD will give a temp C of O but to get final they will need to have an approved working fire alarm monitoring system installed. | |
| 02/17/2015 | FIRE - FINAL | Denied | 1. Install pressure relief valve on riser 2. Paint outside piping to riser 3. Need UL/FM approved fire alarm monitoring system install 4. This building was a "B" occupy but now changed to a I-4 occupy classification, need to install battery back egress lighting per IFC & IBC 1006.3 5. Need to install battery back lighting outside each egress door landing per IBC & IFC 1006.3 #3 . 6. Need fire extinguisher posted every 75' travel distance and one for every 1500 sq. ft of building size. Needs to be a 2A-10BC type. |