Permit: T14CM07503

Parcel: 114469490

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T14CM07503

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2015 FIRE SPKLR - FINAL Approved
02/17/2015 FIRE SPKLR - FINAL Denied Drain test 82-78-82
Fire bell test 38 sec.
1. Install pressure relief valve on riser
2. Paint outside piping to riser
3. Need UL/FM approved fire alarm monitoring system install