Inspection Status: Partial Approval
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/06/2014 |
PLUMBING - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 11/06/2014 |
PLUMBING - FINAL |
|
Partial Approval |
REMOVE SHARP BURRS ON STRUT FOR SAFETY SUPPORT AND SECURE PIPING IN CRAWL SPACE. PROVIDE MIN 1 " CLEARANCE AROUND B VENT TO COMBUSTIBLES. EXTEND B VENT. SINGLE WALL REQ 6" CLR. BOND GAS AT PANEL. PEX PIPING AND NEW WH & FURNACE REW CITY PERMITS & INSPECTIONS |