Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2015 | FIRE SPKLR - FINAL | Approved | ||
| 02/24/2015 | FIRE SPKLR - FINAL | Denied | 1. Need to reinstall the drop ceiling in the pool area or remove the pendent sprinkler heads cannot have both uprights and pendents exposed to each other. 2. Need to reinstall the insulation that is dropping from the deck, insulation is blocking the upright sprinkler coverage. 3. Need annual sprinkler inspection and 5 year check valve inspection completed. |