Permit: T14CM07391

Parcel: 13216600A


Addresses:

4004 S PARK AV 08

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/16/2016 ELECTRIC - FINAL Approved
06/15/2016 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
06/15/2016 ELECTRIC - FINAL Partial Approval 1- ok for approval pending COT B.O. approval of engineers documents concerning seal off and related systems
05/19/2016 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/10/2016 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/19/2016 ELECTRIC - FINAL Partial Approval #1. Verify EPO pushbuttons at the parking light poles are rated for class 1 Div 2 location.
#2. Color code equipment grounds in handholes.
#3.Ground all metalic underground handhole covers, (CNG) building areas (2).
#4. Provide on site test for the service GFI protected main circuit breaker.
#5. Plug all unused openings in conduit and enclosures.
#6. Provide warning labels on service and associated equipment supplied by multiple power sources. ( EM Generator ).
#7. Use approved supports for exposed ground conductors in the new CNG building.
#8. Provide bond bushings at the CNG compressor conduit terminations.
#9. Bond bushings at the parking lot light pole bases loose or not secured properly.
#10. Repair the J-box cover at light pole on the 1st row ( damaged ).
Ref: NEC, art. 110.3, 230, 250, 300, 500 thru 514, 700 thru 702.