Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T14CM07391
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2016 | BUILDING - FINAL | Approved | ||
06/15/2016 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
06/15/2016 | BUILDING - FINAL | Partial Approval | 1- ok for approval pending COT B.O. approval of engineers documents concerning seal off and related systems | |
02/18/2016 | BUILDING - FINAL | Partial Approval | NO GFI MAIN ON PLANS INSPECTION FOR ELECTRICAL 1. LIGHT POLES IN CLASSIFIED AREA AT DISPENSER TO COMPLY WITH WIRING METHODS PER 501 NEC 2. SEALING OF SEAL OFF FITTINGS CANNOT BE PERFORMED PER PRODUCT LISTING AS INSTALLED NEC 110.3 3. EQUIP GROUNDING TO ALL LIGHT POLES 4. ARC FLASH STUDY TO BE SUBMITTED TO AHJ 5. PROVIDE GFI PROTECTED MAIN SERVICE BREAKER AND FIELD TEST AS REQUIRED PER 230-95 NEC 6. GROUND METAL J BX COVERS UNDER GROUND 7. BOND BUUSHINGS REQUIRED AT CLASSIFIED AREA BACK TO SOURCE 501.30 NEC |