Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T14CM07379
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2014 | ELECTRIC - RECONNECT | Approved | ||
| 11/07/2014 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* | |
| 11/07/2014 | ELECTRIC - RECONNECT | Partial Approval | NEUTRAL & HOT ARE BACK WARDS AT SUB PANEL 3 PRONG RECEPTACLES NOT ALLOWED ON NON GROUNDED SYSTEM | |
| 11/03/2014 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/03/2014 | ELECTRIC - RECONNECT | Denied | REPAIR ALL VANDALIZED ELEC WIRING CAP OFF OPEN CONDUCTORS OR INSTALL FIXTURES GROUNDING ELECTRODE CONDUCTORS ARE MISSING. PROVIDE 2 GROUND RODS MIN, 6' APART & REWIRE GROUNDING CONDUCTORS FILL ANY OPEN KROCKNUTS THE PANEL AT REAR OF BLDG IS MISSING SOME BREAKERS |