Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/08/2015 |
MECHANICAL - FINAL |
|
Approved |
|
| 09/01/2015 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 09/01/2015 |
MECHANICAL - FINAL |
|
Partial Approval |
TERMINATE MINI SPLIT CONDENSATE WITH A FITTING. PROVIDE ROOF ACCESS AT PARAPET WALLS. PAINT EXPOSED PVC. SECURE MINI SPLIT CONDENSOR. COAT LINESET. PROVIDE STERILIZATION REPORT AND AIR BALANCE AND BACKFLOW |