Permit: T14CM07313

Parcel: 117132170

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
06/17/2015 FIRE SPKLR - FINAL Approved
05/01/2015 FIRE SPKLR - FINAL Denied NOTE: Sprinkler contractor did not call in on overhead pressure test. However, system has been charged for 5 days and had no leaks.

Denied Final
West wall has insufficient coverage. There is 19 feet between heads close to the wall ( look on plans) and the nearest head centered between them is 9 feet off the wall. Can not have more than 7.6 off wall being that heads are fusable links and not residential extended coverage.
04/28/2015 FIRE SPKLR - FINAL Cancelled PER VOICEMAIL FROM DAVID, THIS WAS A REQUEST FOR A COURTESY INSPECTION TO LOOK AT OVERHEAD PIPING. THE FIRE SPRINKLER CONTRACTOR NEEDS TO CALL IN INSPECTION FROM HIS PERMIT T15BU00437.