Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2015 | FIRE SPKLR - FINAL | Approved | ||
| 05/01/2015 | FIRE SPKLR - FINAL | Denied | NOTE: Sprinkler contractor did not call in on overhead pressure test. However, system has been charged for 5 days and had no leaks. Denied Final West wall has insufficient coverage. There is 19 feet between heads close to the wall ( look on plans) and the nearest head centered between them is 9 feet off the wall. Can not have more than 7.6 off wall being that heads are fusable links and not residential extended coverage. |
|
| 04/28/2015 | FIRE SPKLR - FINAL | Cancelled | PER VOICEMAIL FROM DAVID, THIS WAS A REQUEST FOR A COURTESY INSPECTION TO LOOK AT OVERHEAD PIPING. THE FIRE SPRINKLER CONTRACTOR NEEDS TO CALL IN INSPECTION FROM HIS PERMIT T15BU00437. |