Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM07238
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2015 | FIRE - FINAL | Approved | ||
04/03/2015 | FIRE - FINAL | Partial Approval | Need to call in fire alarm final may stock but can not occupy until alarm finaled. Move exit sign in stock room to S wall arrow on 2 of the merchangt floor exit signs shall point to East exit ( both sides arrow on angled sign pointing to the South Exit monitor is blockin gthe view of the South exit sign |
|
03/23/2015 | FIRE - FINAL | Denied | 1. Taped sprinkler heads on the last sprinkler line next to stock room wall on sales floor. 2. Bent sprinkler head on 2nd sprinkler line from stock room wall 4th head from west wall next to A/C duct work. 3. On 2nd floor in stock room heads to close to wall need to keep 4 inch min to 7'6" max from wall. 4. Inspectors check all sprinkler heads again for tape. |