Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T14CM07238
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2015 | FIRE SPKLR - FINAL | Approved | ||
03/23/2015 | FIRE SPKLR - FINAL | Denied | 1. Taped sprinkler heads on the last sprinkler line next to stock room wall on sales floor. 2. Bent sprinkler head on 2nd sprinkler line from stock room wall 4th head from west wall next to A/C duct work. 3. On 2nd floor in stock room heads to close to wall need to keep 4 inch min to 7'6" max from wall. 4. Inspectors check all sprinkler heads again for tape. |