Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2015 | FIRE SPKLR - FINAL | Approved | ||
| 09/04/2015 | FIRE SPKLR - FINAL | Partial Approval | Sprinkler heads inside of the walk in coolers are red ( 155 degree) type and should be of the green ( 175 degree ) type. |