Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/10/2015 |
FIRE SPKLR - FINAL |
|
Approved |
|
| 09/04/2015 |
FIRE SPKLR - FINAL |
|
Partial Approval |
Sprinkler heads inside of the walk in coolers are red ( 155 degree) type and should be of the green ( 175 degree ) type. |