Permit: T14CM07066

Parcel: 12801005H

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/17/2015 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
03/13/2015 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/13/2015 MECHANICAL - ABOVE CEILING Partial Approval PROVIDE FUSES AT FAN COILS. LABEL FAN COILS. DRAIN PANS MUST EXTEND 1 1/2" PAST ALL SIDES OF FAN COILS. INSULATE ALL SUPPLY & RETURN DUCTS. DUCT SMOKE DETECTORS MUST BE INSTALLED UPSTREAM OF ANY OUTSIDE AIR. PROVIDE MIN 2" BEADED COLLARS ON ALL SUPPLY DIFFUSERS. REPAIR WATER LEAK @ MIXING VALVE. FINISH ELECTRIC J-BOXES ABOVE CEILING.