Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/17/2015 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection :* |
| 03/13/2015 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* |
| 03/13/2015 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
PROVIDE FUSES AT FAN COILS. LABEL FAN COILS. DRAIN PANS MUST EXTEND 1 1/2" PAST ALL SIDES OF FAN COILS. INSULATE ALL SUPPLY & RETURN DUCTS. DUCT SMOKE DETECTORS MUST BE INSTALLED UPSTREAM OF ANY OUTSIDE AIR. PROVIDE MIN 2" BEADED COLLARS ON ALL SUPPLY DIFFUSERS. REPAIR WATER LEAK @ MIXING VALVE. FINISH ELECTRIC J-BOXES ABOVE CEILING. |