Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T14CM07066
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/17/2015 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
03/13/2015 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
03/13/2015 | MECHANICAL - ABOVE CEILING | Partial Approval | PROVIDE FUSES AT FAN COILS. LABEL FAN COILS. DRAIN PANS MUST EXTEND 1 1/2" PAST ALL SIDES OF FAN COILS. INSULATE ALL SUPPLY & RETURN DUCTS. DUCT SMOKE DETECTORS MUST BE INSTALLED UPSTREAM OF ANY OUTSIDE AIR. PROVIDE MIN 2" BEADED COLLARS ON ALL SUPPLY DIFFUSERS. REPAIR WATER LEAK @ MIXING VALVE. FINISH ELECTRIC J-BOXES ABOVE CEILING. |