Permit: T14CM07048

Parcel: 14102013D

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
03/25/2016 FIRE - FINAL Approved
01/07/2016 FIRE - FINAL Partial Approval 1) Need proof that DACT maintains its UL listing with the penetration made for the electrical conduit.
2) Need proof that an AC outlet is allowed inside the DACT.
3) Need proof that transformers can be plugged into outlet and not be in a self enclosure.
-NEC
-UL864
12/24/2015 FIRE - FINAL Partial Approval TCO ok for holiday service.
1) Repair egress light NW corner of building.
2) Repair emergency lights bathrooms.
3) Label electrical room door.
4) Central alarm panel has power strip. Wire properly per NEC.