Permit: T14CM06964

Parcel: 127031260


Addresses:

5822 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
02/03/2015 FIRE - FINAL Approved Drywall needs to be patched, but correct assembly is installed
01/30/2015 FIRE - FINAL Denied Denied. There is a required 2 hour wall between girls dressing and lounge - wall is two hours, but fire rated door is not a fire rated assembly. Door is a 2 min solid wood core, but no fire rating or ul listing on hinges. No fire rating closer although it is ul listed. Advised they need a UL Listed 20 min Fire rated door assembly.
NS - 01/30/15