Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2015 | FIRE - FINAL | Approved | Drywall needs to be patched, but correct assembly is installed | |
| 01/30/2015 | FIRE - FINAL | Denied | Denied. There is a required 2 hour wall between girls dressing and lounge - wall is two hours, but fire rated door is not a fire rated assembly. Door is a 2 min solid wood core, but no fire rating or ul listing on hinges. No fire rating closer although it is ul listed. Advised they need a UL Listed 20 min Fire rated door assembly. NS - 01/30/15 |