Date Description Inspector Results Comments
01/29/2015 PLUMBING - FINAL Approved IVRS - Inspection :*
01/29/2015 PLUMBING - FINAL Approved AIR BALANCE OK. SECURE CONDENSOR ON ROOF. PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX & EXPOSED PVC. PROVIDE A LISTED COVER FOR CONDENSOR. PERMANENTLY I.D. ALL EQUIPMENT ON ROOF. SECURE MIXING VALVES. PROVIDE GRATES AT FLOOR SINKS. PROVIDE BACKFLOW CERTS & STERILIZATION REPORT
01/26/2015 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*