Permit: T14CM06712

Parcel: 133421610


Addresses:

6610 E CALLE LA PAZ

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
10/13/2014 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
10/08/2014 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/08/2014 PLUMBING - GAS PRESSURE TEST Denied CORRECT CONNECTION TO W.H DRAFT DIVERTER, SECURE VENT CONNECTORS REPL LEAKING RELIEF VALVES TERMINATE RELIEF VALVES CONNECT DRYER VENT 3/4' PIPE IS UNDERSIZED AT 50' FOR 138000 BTU PLAN IS IN ACCURATE