Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM06658
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2015 | FIRE - FINAL | Approved | ||
02/11/2015 | FIRE - FINAL | Denied | 1. Correct sprinkler coverage in kitchen closet head is 8'4" away from wall no light hazard rule 2. Exit signs throughout building and stairwell not working repair or replace 3. Battery backup lighting throughout building and stairwell failed to work repair or replace. 4. Repair FDC missing coupling and caps 5. Need annual fire alarm inspection |