Permit: T14CM06498

Parcel: 10511061R

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM06498

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2015 FIRE - FINAL Approved
04/27/2015 FIRE - FINAL Denied 1. Replace painted head in stock room by roll up door
2. Exit door on sales floor south west side has a panic hardware device that has a 15 sec delay device according to the contactor programing was not done for it yet, need to test and make sure when alarm activates that the 15 sec delay shuts off and door opens without a delay.
3. Fire extinguisher in cabinet hard to open need to install a handle on door
4. Fire extinguishers on sale floor cannot see the signage on the beams blocked by stock need to rise the signage above stock so as to see extinguishers from anywhere on the floor.
04/24/2015 FIRE - FINAL Denied DENIED
REPLACE PAINTED SPRINKLER HEAD OVER DUCT WORK IN STORAGE/STOCK AREA.
NS 4/24/15
04/20/2015 FIRE - FINAL Denied 1. Same as last inspection 04.17.2015
2. Need ceiling tiles in storage room northeast room
3. Need signage for fire extinguishers hard to find when blocked by beams
4. Post exit sign over door in warehouse to be seen on both sides hard to see sign when blocked by beam
04/17/2015 FIRE - FINAL Denied 1. Need hardware on exit next to rollup door.
2. Fire extinguishers needed and mounted.
3. Need wall patch next to comm room.