Permit: T14CM06487

Parcel: 140151250


Addresses:

2125 E HOLLADAY ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
12/03/2014 BUILDING - FINAL Approved
12/02/2014 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
12/02/2014 BUILDING - FINAL Not ready for Inspection NO PLANS OR PAPERWORK FOUND - RECALL
10/06/2014 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/06/2014 BUILDING - FINAL Denied 1. EXPOSE FOOTER PER WALL SECTION TO VERIFY 18' DEPTH
2. COMPLETE 3 WAY SWITCH CIRCUIT PER PLAN
3. SECURE ALL ROMEX 8" FROM BOXES THROUGHOUT
4. PANEL SCHEDULE CALLS FOR 2 NEW 20 AMP 12 GUAGE CRAIT 10& 11 IN GUAGE WE INSTALLED
5. PROVIDE CONNECTORS @ LIGHT CONNECTION BOXES
6. MISSING AFECT PER CODE @ CLOSET WALL WEST SIDE
7. INSTALL CAILING FAN BOXES
8. GROUND METER BOXES
9. DUCT WORK NOT INSTALLED
10 MISSING 4+4 WINDOW PER PLAN EAST WALL
STOPPED INSPECTION