Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T14CM06487

Parcel: 140151250


Addresses:

2125 E HOLLADAY ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/31/2014 FRAMING Approved IVRS - Inspection :*
10/30/2014 FRAMING Partial Approval IVRS - Inspection :*
10/06/2014 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/06/2014 FRAMING Denied 1. EXPOSE FOOTER PER WALL SECTION TO VERIFY 18' DEPTH
2. COMPLETE 3 WAY SWITCH CIRCUIT PER PLAN
3. SECURE ALL ROMEX 8" FROM BOXES THROUGHOUT
4. PANEL SCHEDULE CALLS FOR 2 NEW 20 AMP 12 GUAGE CRAIT 10& 11 IN GUAGE WE INSTALLED
5. PROVIDE CONNECTORS @ LIGHT CONNECTION BOXES
6. MISSING AFECT PER CODE @ CLOSET WALL WEST SIDE
7. INSTALL CAILING FAN BOXES
8. GROUND METER BOXES
9. DUCT WORK NOT INSTALLED
10 MISSING 4+4 WINDOW PER PLAN EAST WALL
STOPPED INSPECTION