Permit: T14CM06281

Parcel: 13316048B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
02/10/2015 FIRE - FINAL Approved All emergency lighting working on AC shut down. Exit sign backup power is working.
Suite number is installed on doors.
02/09/2015 FIRE - FINAL Partial Approval Pending:
Suite numbers need to be posted on doors
shut down of electric to verify emergency lighting and back up exit sign battery operational.
02/04/2015 FIRE - FINAL Partial Approval NOT READY called for information only
12/29/2014 FIRE - FINAL Partial Approval Partial Approval Okay to use Phase #1 but to get fire final after Phase #2 the following shall be completed:
1. IFC 505.1 (Modifications) Address numbers shall be displayed and visible from both street directions of approaching vehicles (numbers post on Tanque Verde side).
2. Shall post exit signs showing where 2nd exit is located on both sides of building (i.e. phase 1 and phase 2).
3. All Gates out of the atrium area to a public way are not allowed to have double cylinder keyed locking device only thumb style (ΒΌ turn lock).
4. Need to install emergency backup lighting per IFC 1006.3