Permit: T14CM06178

Parcel: 110030020


Addresses:

3930 E KLEINDALE RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/02/2016 MECHANICAL - FINAL Approved IVRS - Inspection :$
04/08/2016 MECHANICAL - FINAL Denied IVRS - Inspection :23No Description.| 99946
*
04/08/2016 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
11/25/2015 MECHANICAL - FINAL Not ready for Inspection INSPECTION WAS NOT DONE TENANTS SAID THE ITEMS WERE NOT FIXED AND THEY HAD TO BE IN COURT DID NOT LET INSPECTOR IN
09/18/2015 MECHANICAL - FINAL Denied SINGLE WALL VENT REQUIRES MIN 6"CLEARANCE FROM ARMAFLEX. CAP OFF VENT UPSTREAM OF CONDENSATE TRAP. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. PROVIDE A PROTECTIVE COATING ON ALL OF EXPOSED ARMAFLEX ON ROOF. PLASTIC HOSE NOT ALLOWED OUTDOORS. PROVIDE GRILLES AT ALL SUPPLY OUTLETS WITH DAMPERS