Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM06131
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/01/2015 | FIRE - FINAL | Approved | ||
06/30/2015 | FIRE - FINAL | Partial Approval | PARTIAL APPROVAL 1. still need to pass fire alarm final ( all horns strobes need to operate) 2. keys for lock box 3. FDC sign to be posted on building near FDC's and Riser Room 4. Need 1 more extinguisher in receiving/storage area. *Already passed emergency lighting test and exit sign back up power test. |