Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2014 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/28/2014 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/27/2014 | ELECTRIC - FINAL | Denied | 1. CIRCUIT #12 NOT GFCI PROTECTED ON PANEL SCHEDULE 2. CIRCUIT #4 NOT GFCI PROTECTED ON PANEL SCHEDULE 3. SUBMIT AS BUILT OR BUILD TO PLAN REFEE |
|
| 10/24/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/23/2014 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |