Permit: T14CM06016

Parcel: 13014439B


Addresses:

4426 E 22ND ST


Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T14CM06016

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
10/06/2015 FIRE SPKLR - OH PIPING & HYDRO Approved
08/10/2015 FIRE SPKLR - OH PIPING & HYDRO Not ready for Inspection
08/06/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval pressure tested the pipe and heads over the car wash ( south side) passed at 225 psi ( held more than 2 hours). Heads now installed under the stairs/landings.
head installed in office closet, in alcove near elevator.

Head still plugged on second floor in tire storage.
07/28/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Install heads under Stairs/landings ( documented on plans where), Per NFPA 13 Section 8.10.6.3.2
2. Pressure test conducted on all portions of the building except: car wash bays where no pipe installed ( noted on plans)
3. Install heads missing in alcove near elevator and in closet in offices ( downstairs & upstairs)
place head where plugged ( upstairs in area hear tire machine)