Inspection History: FIRE SPKLR - UG PIPING FLUSH
Permit Number - T14CM06016
Inspection Description - FIRE SPKLR - UG PIPING FLUSH
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2015 | FIRE SPKLR - UG PIPING FLUSH | Approved | Flushed 3 times for 1 minute. First with Burlap - some debris second without burlap, one minute more. Third with burlap - ran clean 1 minute, no debris in bag. Approved. |
|
08/12/2015 | FIRE SPKLR - UG PIPING FLUSH | Denied | Not done due piping not connected to riser | |
08/10/2015 | FIRE SPKLR - UG PIPING FLUSH | Denied | STILL NEED TO BE FLUSHED | |
08/04/2015 | FIRE SPKLR - UG PIPING FLUSH | Denied | The contractors plans state that a separate permit shall be pulled for the installation of the underground ( from Tucson Water to the stub up for the riser). The general contractor called in an UG piping and hydro and an UG flush for today and further research shows no permit was pulled. Work has been completed by Eagle Rock and has already backfilled. A permit shall be pulled, Plans shall be submitted and the underground shall be exposed for visual inspection before hydro and the flush shall be approved. |