Permit: T14CM06016

Parcel: 13014439B


Addresses:

4426 E 22ND ST


Inspection Status: Approved

Inspection History: FIRE SPKLR - UG PIPING FLUSH

Permit Number - T14CM06016

Inspection Description - FIRE SPKLR - UG PIPING FLUSH

Inspection Status - Approved

Date Description Inspector Results Comments
08/19/2015 FIRE SPKLR - UG PIPING FLUSH Approved Flushed 3 times for 1 minute. First with Burlap - some debris
second without burlap, one minute more. Third with burlap - ran clean 1 minute, no debris in bag.
Approved.
08/12/2015 FIRE SPKLR - UG PIPING FLUSH Denied Not done due piping not connected to riser
08/10/2015 FIRE SPKLR - UG PIPING FLUSH Denied STILL NEED TO BE FLUSHED
08/04/2015 FIRE SPKLR - UG PIPING FLUSH Denied The contractors plans state that a separate permit shall be pulled for the installation of the underground ( from Tucson Water to the stub up for the riser). The general contractor called in an UG piping and hydro and an UG flush for today and further research shows no permit was pulled. Work has been completed by Eagle Rock and has already backfilled. A permit shall be pulled, Plans shall be submitted and the underground shall be exposed for visual inspection before hydro and the flush shall be approved.