Permit: T14CM05968

Parcel: 12509141A


Addresses:

2901 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/26/2015 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/14/2014 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/14/2014 MECHANICAL - FINAL Denied 1. PROVIDE APPROVED MEANS LABELING UNIT (SHARPIE NOT APPROVED)
2. PROVIDE MINIMUM 2" (R-8) DUCT INSULATION ON ALL ROOF TOP DUCT WORK S/A CURRENTLY 20X12 O.D
3. PROVIDE 3' CLEARNACE AT RTU DISCONECT