Inspection History Details
Inspection Status: Approved
Inspection History: SITE - SEWER
Permit Number - T14CM05877
Inspection Description - SITE - SEWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2015 | SITE - SEWER | Approved | IVRS - Inspection :* | |
04/21/2015 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* | |
04/09/2015 | SITE - SEWER | Partial Approval | IVRS - Inspection :* | |
04/09/2015 | SITE - SEWER | Partial Approval | PIPING OK. PROVIDE A DIRECTIONAL FITTING AT MAIN SEWER CONNECTION. TEST INTERCEPTOR CONNECTIONS | |
04/08/2015 | SITE - SEWER | Partial Approval | IVRS - Inspection :* | |
04/07/2015 | SITE - SEWER | Partial Approval | TEST ON GW FROM "B" TO INTERCEPTOR, OR, MAKE EACH CONNECTION. USE THIN WALL BUSHING AT BUILDING. TEST INTERCEPTOR PIPE CONNECTIONS. TEST ON SANITARY DOWN STREAM OF INTERCEPTOR TO BRANCH COND. | |
04/03/2015 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* | |
04/02/2015 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* | |
04/02/2015 | SITE - SEWER | Not ready for Inspection | COMPLETE PIPING. CORRECT TRANSITION COUPLING. PROVIDE A WATER TEST |