Permit: T14CM05749

Parcel: 12709009D

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T14CM05749

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
10/22/2014 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
10/16/2014 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
10/16/2014 PLUMBING - GAS PRESSURE TEST Partial Approval PROVIDE MIN 10LB TEST ON GAS PIPING. PROVIDE MIN 1/8" PER FIT SLOPE ON CONDENSATE DRAINS, USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE