Permit: T14CM05738

Parcel: 132090190

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/02/2015 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/22/2015 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/22/2015 ELECTRIC - FINAL Denied 1. ACORN GROUND RODS
2. LABEL CIRCUITS
3. SMOKE ALARMS HALLWAYS
4. PROVIDE LETTERHEAD FROM LICENSED ELECTRICAL CONTRACTOR STATING ALL REPAIRS DUE TO VANDALISM ARE TO CODE FOR SAFETY
5. WHITE HOT LEADS TO BE BLACK OR RED (TAPE OK)
01/16/2015 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/16/2015 ELECTRIC - FINAL Denied SEE NOTES 3076
01/16/2015 ELECTRIC - FINAL Denied - EXPOSE ALL GROUND RODS FOR INSPECTION - 1 #4 PER ACORN CONNECTOR AT GROUND ROD - 2 GROUND RODS 6' MIN APART - EXPOSE #4 BARE
- ADDRESS LABELS (PERMANENT)
- NEW WIRING INSIDE UNITS REQUIRES APPROVED PLANS & PERMIT, APPROVED INSPECTIONS
- PHONE # OF RECORD NOT CORRECT