Permit: T14CM05731

Parcel: 133124550

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T14CM05731

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/17/2014 PLUMBING - FINAL Approved IVRS - Inspection :*
11/14/2014 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
11/10/2014 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
11/10/2014 PLUMBING - FINAL Not ready for Inspection PLANS & PERMITS REQ FOR INSP PROVIDE STERLIZIATION DOCUMENTATION
11/07/2014 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/07/2014 PLUMBING - FINAL Denied CORRECT MAKE-UP ON PEX FITTING OVERHEAD REMOVE WOOD BELOW FLOOR WATER PROOF & SECURE FLOOR ACCESS PANEL. PROVIDE ACCESS TO FLOW CONT. PANT OF VENT AT HS SHALL NOT BE BELOW TRAP WER 909.2 INDIRECT PIPING EXCEDING 30" REQ TRAP 802.2 CLEAN OUT COVERS ON SMOTH WALLS PLUG SHALL BE LISTED & SEALED USE DRAINAGE FITTING AS REQ. 3 COMP SINK REQ. SEPRATE INDIRECT DRAINS WH RELIEF DRAIN SHALL BE MATERIAL FOR DOMESTIC HW PIPING W/OUT INSERT MIN AIR CAP IS 2x DIAMESTER SEAL FIXTURES AT WALL