Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2014 | FIRE - FINAL | Approved | ||
| 10/22/2014 | FIRE - FINAL | Denied | 1. Need repair or replace exit sign over front entrance emergency light failed 2. Post 2 fire extinguishers 2A-10BC type one by rear door and one by the main entrance 3. Need duct work install so as the inspector can make sure duct work does not block sprinkler coverage 4. Posted suite numbers on front window |
|