Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/22/2014 | FIRE SPKLR - FINAL | Approved | ||
| 10/20/2014 | FIRE SPKLR - FINAL | Denied | In bathroom sprinkler head needs to be corrected almost pulled above sheet rock ceiling and sitting against sheet rock breaking up spray pattern. | |
| 10/10/2014 | FIRE SPKLR - FINAL | Denied | 1. No one on site at 10:30am. 2. Need sub to call in sprinkler inspection. |