Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/12/2014 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection :* |
| 12/10/2014 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 12/10/2014 |
BUILDING - FINAL |
|
Partial Approval |
PROVIDE ARC FAULT BREAKERS & TAMPER-PROOF RECEPTACLES AS PER NOTE #12 ON THE PLANS & PER 2012 IRC. TERMINATE CONDENSATE TO 6" OF THE GROUND. BLOCK PVC EVERY 4'. MARK A/C UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. CAP-OFF WATERLINE ON ROOF. CAP-OFF UNUSED GASLINE AT LAUNDRY. KITCHEN SINK DRAIN HAS BACK PITCH. |