Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T14CM05636

Parcel: 119223290


Addresses:

2031 W TOURNEY RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/17/2014 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/02/2014 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/02/2014 ELECTRIC - FINAL Denied 1. RESUPPORT METER BASE TO STRUCTURE
2. INSTALL 2 GROUND RODS 6' APART BOND WATER AND GAS PIPING
3. INSTALL BOND BUSHING ON RIGID NIPPLE BETWEEN METER AND PANEL
4. INSTALL PERMANENT ADDRESS LABEL ON SERVICE
NOTE: SERVICE REENERGIZED PRIOR TO INSPECTORS APPROVAL