Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2014 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/02/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/02/2014 | ELECTRIC - FINAL | Denied | 1. RESUPPORT METER BASE TO STRUCTURE 2. INSTALL 2 GROUND RODS 6' APART BOND WATER AND GAS PIPING 3. INSTALL BOND BUSHING ON RIGID NIPPLE BETWEEN METER AND PANEL 4. INSTALL PERMANENT ADDRESS LABEL ON SERVICE NOTE: SERVICE REENERGIZED PRIOR TO INSPECTORS APPROVAL |