Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/26/2014 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/24/2014 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 11/24/2014 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | 1. OPEN BOSS ABOVE CEIELING 2. PROVIDE MINIMUM 3 SCREWS ON STRAPS PER SMACNA, PROVIDE BEADED CEILING AT ALL FLEX CONNECTIONS 3. WORK NOT COMPLETED 4. PROVIDE APPROVED COLLARS AT FLEX TAKE OFF, MAX FLEX LENGHT 8-M2 107 FOLLOW DETAIL AT ALL POINTS |